CVE-2026-16438

An arbitrary operation vulnerability in GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI, and MC Works64

Incorrect Privilege Assignment vulnerability in Mitsubishi Electric GENESIS64 versions 10.97.3 and prior, ICONICS Suite versions 10.97.3 and prior, Hyper Historian versions 10.97.3 and prior, AnalytiX versions 10.97.3 and prior, MobileHMI 10.97.3 and prior, MC Works64 all versions, Mitsubishi Electric Iconics Digital Solutions GENESIS64 versions 10.97.3 and prior, ICONICS Suite versions 10.97.3 and prior, Hyper Historian versions 10.97.3 and prior, AnalytiX versions 10.97.3 and prior, and MobileHMI 10.97.3 and prior allows an attacker who can log in using the same administrator account for the affected products to launch and operate DCOM objects locally or remotely. During installation, the installers of the affected products unnecessarily grant default DCOM permissions to the administrator account of the affected products. Users with that administrator accounts can locally or remotely launch and operate DCOM objects that should require UAC elevation. As a result, the attacker may disclose, tamper with, destroy, or delete internal information, or cause the affected system to enter a denial-of-service (DoS) condition.

CVSS 4.0 · 9.4 Critical EPSS < 1% KEV · Not listed
Products
CVE-2026-15688

Password Authentication Bypass Vulnerability in GX Works3 and Motion Control Setting

Incorrect Implementation of Authentication Algorithm Vulnerability in Mitsubishi Electric GX Works3 and Motion Control Setting allows a local attacker to successfully authenticate even with an invalid block password by executing the affected product and modifying part of the executable module in memory, and thereby may be able to view, tamper with, destroy, or delete control programs.

CVSS 4.0 · 9.2 Critical EPSS < 1% KEV · Not listed
CVE-2023-5275

Improper Input Validation vulnerability in simulation function of GX Works2 allows an attacker to cause a denial-of-service (DoS) condition on the function by sending specially crafted packets. However, the attacker would need to send the packets from within the same personal computer where the function is running.

CVSS 3.1 · 2.5 Low EPSS < 1% KEV · Not listed
Products
CVE-2023-5274

Improper Input Validation vulnerability in simulation function of GX Works2 allows an attacker to cause a denial-of-service (DoS) condition on the function by sending specially crafted packets. However, the attacker would need to send the packets from within the same personal computer where the function is running.

CVSS 3.1 · 2.5 Low EPSS < 1% KEV · Not listed
Products
CVE-2022-24946

Improper Resource Locking vulnerability in Mitsubishi Electric MELSEC iQ-R Series R12CCPU-V firmware versions "16" and prior, Mitsubishi Electric MELSEC-Q Series Q03UDECPU the first 5 digits of serial No. "24061" and prior, Mitsubishi Electric MELSEC-Q Series Q04/06/10/13/20/26/50/100UDEHCPU the first 5 digits of serial No. "24061" and prior, Mitsubishi Electric MELSEC-Q Series Q03/04/06/13/26UDVCPU the first 5 digits of serial number "24051" and prior, Mitsubishi Electric MELSEC-Q Series Q04/06/13/26UDPVCPU the first 5 digits of serial number "24051" and prior, Mitsubishi Electric MELSEC-Q Series Q12DCCPU-V all versions, Mitsubishi Electric MELSEC-Q Series Q24DHCCPU-V(G) all versions, Mitsubishi Electric MELSEC-Q Series Q24/26DHCCPU-LS all versions, Mitsubishi Electric MELSEC-L series L02/06/26CPU(-P) the first 5 digits of serial number "24051" and prior, Mitsubishi Electric MELSEC-L series L26CPU-(P)BT the first 5 digits of serial number "24051" and prior and Mitsubishi Electric MELIPC Series MI5122-VW firmware versions "05" and prior allows a remote unauthenticated attacker to cause a denial of service (DoS) condition in Ethernet communications by sending specially crafted packets. A system reset of the products is required for recovery.

CVSS 3.1 · 7.5 High EPSS 1.8% KEV · Not listed
Products
CVE-2026-1874

Denial-of-Service (DoS) vulnerability in Ethernet function of MELSEC iQ-F Series EtherNet/IP module and Ethernet module

Always-Incorrect Control Flow Implementation vulnerability in Mitsubishi Electric Corporation MELSEC iQ-F Series FX5-ENET/IP Ethernet Module FX5-ENET/IP versions 1.106 and prior and Mitsubishi Electric Corporation MELSEC iQ-F Series FX5-EIP EtherNet/IP Module FX5-EIP versions 1.000 and prior allows a remote attacker to cause a denial-of-service (DoS) condition on the products by continuously sending UDP packets to the products. A system reset of the product is required for recovery.

CVE-2026-1876

Denial-of-Service (DoS) vulnerability in Ethernet function of MELSEC iQ-F Series Ethernet module

Improper Resource Shutdown or Release vulnerability in Mitsubishi Electric Corporation MELSEC iQ-F Series FX5-ENET/IP Ethernet Module FX5-ENET/IP all versions allows a remote attacker to cause a denial-of-service (DoS) condition on the products by continuously sending UDP packets to the products. A system reset of the product is required for recovery.

CVE-2026-1875

Denial-of-Service (DoS) vulnerability in Ethernet function of MELSEC iQ-F Series EtherNet/IP module

Improper Resource Shutdown or Release vulnerability in Mitsubishi Electric Corporation MELSEC iQ-F Series FX5-EIP EtherNet/IP Module FX5-EIP versions 1.000 and prior allows a remote attacker to cause a denial-of-service (DoS) condition on the products by continuously sending UDP packets to the products. A system reset of the product is required for recovery.

CVE-2025-7376

Information Tampering Vulnerability in Multiple Processes of GENESIS64, ICONICS Suite, MobileHMI, Hyper Historian, AnalytiX, IoTWorX, MC Works64, and GENESIS

Windows Shortcut Following (.LNK) vulnerability in multiple processes of Mitsubishi Electric GENESIS64 versions 10.97.3 and prior, Mitsubishi Electric ICONICS Suite versions 10.97.3 and prior, Mitsubishi Electric MobileHMI versions 10.97.3 and prior, Mitsubishi Electric Hyper Historian versions 10.97.3 and prior, Mitsubishi Electric AnalytiX versions 10.97.3 and prior, Mitsubishi Electric IoTWorX version 10.95, Mitsubishi Electric GENESIS version 11.00, Mitsubishi Electric MC Works64 all versions, Mitsubishi Electric Iconics Digital Solutions GENESIS64 versions 10.97.3 and prior, Mitsubishi Electric Iconics Digital Solutions ICONICS Suite versions 10.97.3 and prior, Mitsubishi Electric Iconics Digital Solutions MobileHMI versions 10.97.3 and prior, Mitsubishi Electric Iconics Digital Solutions Hyper Historian versions 10.97.3 and prior, Mitsubishi Electric Iconics Digital Solutions AnalytiX versions 10.97.3 and prior, Mitsubishi Electric Iconics Digital Solutions IoTWorX version 10.95, and Mitsubishi Electric Iconics Digital Solutions GENESIS version 11.00 allows a local authenticated attacker to make an unauthorized write to arbitrary files, by creating a symbolic link from a file used as a write destination by the processes of the affected products to a target file. This could allow the attacker to destroy the file on a PC with the affected products installed, resulting in a denial-of-service (DoS) condition on the PC if the destroyed file is necessary for the operation of the PC.

CVSS 3.1 · 5.9 Medium EPSS < 1% KEV · Not listed
CVE-2025-3128

Mitsubishi Electric Europe smartRTU OS Command Injection

A remote unauthenticated attacker who has bypassed authentication could execute arbitrary OS commands to disclose, tamper with, destroy or delete information in Mitsubishi Electric smartRTU, or cause a denial-of service condition on the product.

CVSS 4.0 · 9.3 Critical EPSS < 1% KEV · Not listed
Products
CVE-2025-11009

Information Disclosure Vulnerability in GT Designer3

Cleartext Storage of Sensitive Information vulnerability in Mitsubishi Electric GT Designer3 Version1 (GOT2000) all versions and Mitsubishi Electric GT Designer3 Version1 (GOT1000) all versions allows a local unauthenticated attacker to obtain plaintext credentials from the project file for GT Designer3. This could allow the attacker to operate illegally GOT2000 series or GOT1000 series by using the obtained credentials.

CVSS 3.1 · 5.1 Medium EPSS < 1% KEV · Not listed
Products
CVE-2025-3232

Mitsubishi Electric Europe smartRTU Missing Authentication for Critical Function

A remote unauthenticated attacker may be able to bypass authentication by utilizing a specific API route to execute arbitrary OS commands.

CVSS 4.0 · 8.7 High EPSS < 1% KEV · Not listed
Products
CVE-2024-1574

Use of Externally-Controlled Input to Select Classes or Code ('Unsafe Reflection') vulnerability in the licensing feature of Mitsubishi Electric GENESIS64 versions 10.97.2 and prior, Mitsubishi Electric ICONICS Suite versions 10.97.2 and prior, Mitsubishi Electric Hyper Historian versions 10.97.2 and prior, Mitsubishi Electric AnalytiX versions 10.97.2 and prior, Mitsubishi Electric MobileHMI versions 10.97.2 and prior, Mitsubishi Electric MC Works64 all versions, Mitsubishi Electric GENESIS32 versions 9.7 and prior, Mitsubishi Electric BizViz versions 9.7 and prior, Mitsubishi Electric Iconics Digital Solutions GENESIS64 versions 10.97.2 and prior, Mitsubishi Electric Iconics Digital Solutions ICONICS Suite versions 10.97.2 and prior, Mitsubishi Electric Iconics Digital Solutions Hyper Historian versions 10.97.2 and prior, Mitsubishi Electric Iconics Digital Solutions AnalytiX versions 10.97.2 and prior, Mitsubishi Electric Iconics Digital Solutions MobileHMI versions 10.97.2 and prior, Mitsubishi Electric Iconics Digital Solutions GENESIS32 versions 9.7 and prior, and Mitsubishi Electric Iconics Digital Solutions BizViz versions 9.7 and prior allows a local attacker to execute a malicious code with administrative privileges by tampering with a specific file that is not protected by the system.

CVSS 3.1 · 6.7 Medium EPSS < 1% KEV · Not listed
CVE-2024-8299

Malicious Code Execution Vulnerability in GENESIS64, ICONICS Suite, Hyper Historian, MC Works64, and GENESIS32

Uncontrolled Search Path Element vulnerability in Mitsubishi Electric GENESIS64 versions 10.97.3 and prior, Mitsubishi Electric ICONICS Suite versions 10.97.3 and prior, Mitsubishi Electric Hyper Historian versions 10.97.3 and prior, Mitsubishi Electric GENESIS32 all versions, Mitsubishi Electric MC Works64 all versions, Mitsubishi Electric Iconics Digital Solutions GENESIS64 versions 10.97.3 and prior, Mitsubishi Electric Iconics Digital Solutions ICONICS Suite versions 10.97.3 and prior, Mitsubishi Electric Iconics Digital Solutions Hyper Historian versions 10.97.3 and prior, and Mitsubishi Electric Iconics Digital Solutions GENESIS32 all versions allows a local authenticated attacker to execute a malicious code by storing a specially crafted DLL in a specific folder. This could lead to disclose, tamper with, destroy, or delete information in the affected products, or to cause a denial of service (DoS) condition on the products.

CVSS 3.1 · 7.8 High EPSS < 1% KEV · Not listed
CVE-2025-8531

Improper Handling of Length Parameter Inconsistency vulnerability in Mitsubishi Electric Corporation MELSEC-Q Series Q03UDVCPU, Q04UDVCPU, Q06UDVCPU, Q13UDVCPU, Q26UDVCPU, Q04UDPVCPU, Q06UDPVCPU, Q13UDPVCPU, and Q26UDPVCPU with the first 5 digits of serial No. "24082" to "27081" allows a remote attacker to cause an integer underflow by sending specially crafted packets to the affected product to stop Ethernet communication and the execution of control programs on the product, when the user authentication function is enabled. The user authentication function is enabled by default only when settings are configured by GX Works2, which complies with the Cybersecurity Law of the People's Republic of China, and is normally disabled.

CVSS 3.1 · 6.8 Medium EPSS 1.1% KEV · Not listed
CVE-2024-1573

Missing Authentication for Critical Function vulnerability in the mobile monitoring feature of Mitsubishi Electric GENESIS64 versions 10.97.2 and prior, Mitsubishi Electric ICONICS Suite versions 10.97.2 and prior, Mitsubishi Electric Hyper Historian versions 10.97.2 and prior, Mitsubishi Electric AnalytiX versions 10.97.2 and prior, Mitsubishi Electric MobileHMI versions 10.97.2 and prior, Mitsubishi Electric IoTWorX version 10.95, Mitsubishi Electric MC Works64 all versions, Mitsubishi Electric Iconics Digital Solutions GENESIS64 versions 10.97.2 and prior, Mitsubishi Electric Iconics Digital Solutions ICONICS Suite versions 10.97.2 and prior, Mitsubishi Electric Iconics Digital Solutions Hyper Historian versions 10.97.2 and prior, Mitsubishi Electric Iconics Digital Solutions AnalytiX versions 10.97.2 and prior, Mitsubishi Electric Iconics Digital Solutions MobileHMI versions 10.97.2 and prior, and Mitsubishi Electric Iconics Digital Solutions IoTWorX version 10.95 allows a remote unauthenticated attacker to bypass proper authentication and log in to the system when all of the following conditions are met: (1) Active Directory is used in the security setting (2) "Automatic log in" option is enabled in the security setting (3) The IcoAnyGlass IIS Application Pool is running under an Active Directory Domain Account. (4) The IcoAnyGlass IIS Application Pool account is included in GENESIS64, ICONCIS Suite, and MC Works64 Security and has permission to log in.

CVSS 3.1 · 5.9 Medium EPSS < 1% KEV · Not listed
CVE-2024-1182

Uncontrolled Search Path Element vulnerability in Mitsubishi Electric GENESIS64 versions 10.97.3 and prior, Mitsubishi Electric ICONICS Suite versions 10.97.3 and prior, Mitsubishi Electric Hyper Historian versions 10.97.3 and prior, Mitsubishi Electric MC Works64 all versions, Mitsubishi Electric GENESIS32 versions 9.7 and prior, Mitsubishi Electric Iconics Digital Solutions GENESIS64 versions 10.97.3 and prior, Mitsubishi Electric Iconics Digital Solutions ICONICS Suite versions 10.97.3 and prior, Mitsubishi Electric Iconics Digital Solutions Hyper Historian versions 10.97.3 and prior, and Mitsubishi Electric Iconics Digital Solutions GENESIS32 versions 9.7 and prior allows a local attacker to execute a malicious code by storing a specially crafted DLL in a specific folder when GENESIS64, ICONICS Suite, Hyper Historian, GENESIS32, and MC Works64 are installed with the Pager agent in the alarm multi-agent notification feature.

CVSS 3.1 · 7 High EPSS < 1% KEV · Not listed
CVE-2024-8300

Malicious Code Execution Vulnerability in GENESIS64 and ICONICS Suite

Dead Code vulnerability in Mitsubishi Electric GENESIS64 Version 10.97.2, 10.97.2 CFR1, 10.97.2 CRF2 and 10.97.3, Mitsubishi Electric Iconics Digital Solutions GENESIS64 Version 10.97.2, 10.97.2 CFR1, 10.97.2 CRF2 and 10.97.3, Mitsubishi Electric ICONICS Suite Version 10.97.2, 10.97.2 CFR1, 10.97.2 CRF2 and 10.97.3, and Mitsubishi Electric Iconics Digital Solutions ICONICS Suite Version 10.97.2, 10.97.2 CFR1, 10.97.2 CRF2 and 10.97.3 allows a local authenticated attacker to execute a malicious code by tampering with a specially crafted DLL. This could lead to disclose, tamper with, destroy, or delete information in the affected products, or cause a denial of service (DoS) condition on the products.

CVSS 3.1 · 7 High EPSS < 1% KEV · Not listed
Products
CVE-2021-47884

Configuration Tool 1.6.53 - 'OpLclSrv' Unquoted Service Path

OKI Configuration Tool 1.6.53 contains an unquoted service path vulnerability in the OKI Local Port Manager service that allows local attackers to potentially execute arbitrary code. Attackers can exploit the unquoted path in 'C:\Program Files\Okidata\Common\extend3\portmgrsrv.exe' to inject malicious executables and escalate privileges.

CVSS 4.0 · 8.5 High EPSS < 1% KEV · Not listed
CVE-2025-3784

Information Disclosure Vulnerability in GX Works2

Cleartext Storage of Sensitive Information Vulnerability in GX Works2 all versions allows an attacker to disclose credential information stored in plaintext from project files. As a result, the attacker may be able to open project files protected by user authentication using disclosed credential information, and obtain or modify project information.

CVSS 3.1 · 5.5 Medium EPSS < 1% KEV · Not listed
Products