Search vulnerabilities

Results 11

Export CSV
CVE-2016-0867

CAREL PlantVisorEnhanced allows remote attackers to bypass intended access restrictions via a direct file request.

CVSS 3.0 · 7.5 High EPSS 2.2% KEV · Not listed
Vendors
CVE-2011-3487

Directory traversal vulnerability in CarelDataServer.exe in Carel PlantVisor 2.4.4 and earlier allows remote attackers to read arbitrary files via a .. (dot dot) in an HTTP GET request.

CVSS 2.0 · 5.0 Medium EPSS 7.4% KEV · Not listed
Vendors
Products
CVE-2023-3643

Boss Mini document file inclusion

A vulnerability was found in Boss Mini 1.4.0 Build 6221. It has been classified as critical. This affects an unknown part of the file boss/servlet/document. The manipulation of the argument path leads to file inclusion. It is possible to initiate the attack remotely. The exploit has been disclosed to the public and may be used. The identifier VDB-233889 was assigned to this vulnerability.

CVSS 3.1 · 7.3 High EPSS 75.4% KEV · Not listed
Vendors
CVE-2022-37122

Carel pCOWeb HVAC BACnet Gateway 2.1.0, Firmware: A2.1.0 - B2.1.0, Application Software: 2.15.4A Software v16 13020200 suffers from an unauthenticated arbitrary file disclosure vulnerability. Input passed through the 'file' GET parameter through the 'logdownload.cgi' Bash script is not properly verified before being used to download log files. This can be exploited to disclose the contents of arbitrary and sensitive files via directory traversal attacks.

CVSS 3.1 · 7.5 High EPSS 23.5% KEV · Not listed
Vendors
CVE-2019-9484

The Glen Dimplex Deutschland GmbH implementation of the Carel pCOWeb configuration tool allows remote attackers to obtain access via an HTTP session on port 10000, as demonstrated by reading the modem password (which is 1234), or reconfiguring "party mode" or "vacation mode."

CVSS 3.0 · 7.5 High EPSS 1.5% KEV · Not listed
Vendors
CVE-2019-13553

Rittal Chiller SK 3232-Series web interface as built upon Carel pCOWeb firmware A1.5.3 – B1.2.4. The authentication mechanism on affected systems is configured using hard-coded credentials. These credentials could allow attackers to influence the primary operations of the affected systems, namely turning the cooling unit on and off and setting the temperature set point.

CVSS 3.1 · 9.8 Critical EPSS 2.3% KEV · Not listed
Vendors
CVE-2019-13549

Rittal Chiller SK 3232-Series web interface as built upon Carel pCOWeb firmware A1.5.3 – B1.2.4. The authentication mechanism on affected systems does not provide a sufficient level of protection against unauthorized configuration changes. Primary operations, namely turning the cooling unit on and off and setting the temperature set point, can be modified without authentication.

CVSS 3.1 · 7.5 High EPSS 1.0% KEV · Not listed
Vendors
CVE-2019-11369

An issue was discovered in Carel pCOWeb prior to B1.2.4. In /config/pw_changeusers.html the device stores cleartext passwords, which may allow sensitive information to be read by someone with access to the device.

CVSS 3.0 · 8.8 High EPSS 8.1% KEV · Not listed
Vendors