RPC session pool exhausted by unfinished fragmented requests
Default status is the baseline for the product, each version can override it (e.g. patched versions marked unaffected).
| Vendor | Product | Default status | Versions | ||||||
|---|---|---|---|---|---|---|---|---|---|
| RT-Labs | P-Net | unaffected |
|
No data.
No data.
No data available yet.
Vendor Solution
Upgrade to P-Net 1.0.4 or later.
No CVSS v3.1
No CVSS v3.0
No CVSS v2
This CVE is not in the KEV list.
No EPSS score available.
Key SSVC decision points have not yet been added.
| Type | Values Removed | Values Added |
|---|---|---|
| Description | P-Net before 1.0.4 keeps the RPC session that is allocated for a fragment of a request with an unknown activity UUID, without a timeout, when the rest of the request never arrives. A session that does not get an Application Relationship is also kept after the response. Repeated fragments or requests with different activity UUIDs exhaust the available sessions, one UDP packet per session. Once they are exhausted the device no longer answers a Connect request until it is restarted. An unauthenticated attacker with ADJACENT network access can use this to cause a denial of service. | |
| Title | RPC session pool exhausted by unfinished fragmented requests | |
| Weaknesses | CWE-772 | |
| References |
| |
| Metrics |
cvssV4_0
|
No data.