CVE-2025-3756

Denial of Service Vulnerabilities in System 800xA, Symphony® Plus IEC 61850

Published Apr 13, 2026 CVSS 4.0 · 7.1 High EPSS < 1% KEV · Not listed
Description
A vulnerability exists in the command handling of the IEC 61850 communication stack included in the product revisions listed as affected in this CVE. An attacker with access to IEC 61850 networks could exploit the vulnera bility by using a specially crafted 61850 packet, forcing the communication interfaces of the PM 877, CI850 and CI868 modules into fault mode or causing unavailability of the S+ Operations 61850 connectivity, resulting in a denial-of-service situation. 




The System 800xA IEC61850 Connect is not affected. Note: This vulnerability does not impact on the overall availability and functionality of the S+ Operations node, only the 61850 communication function.

   



This issue affects AC800M (System 800xA): from 6.0.0x through 6.0.0303.0, from 6.1.0x through 6.1.0031.0, from 6.1.1x through 6.1.1004.0, from 6.1.1x through 6.1.1202.0, from 6.2.0x through 6.2.0006.0; Symphony Plus SD Series: A_0, A_1, A_2.003, A_3.005, A_4.001, B_0.005; Symphony Plus MR (Melody Rack): from 3.10 through 3.52; S+ Operations: 2.1, 2.2, 2.3, 3.3.

Remediation

No solution or workaround provided in the CVE record

Tracking

Sign in to view the affected projects.

Advisories

No advisories available
History
Type Values Removed Values Added
First Time appeared Abb
Abb 800xa System
Abb symphony + Operations
Abb symphony Plus Mr (melody Rack)
Abb symphony Plus Sd Series
Vendors & Products Abb
Abb 800xa System
Abb symphony + Operations
Abb symphony Plus Mr (melody Rack)
Abb symphony Plus Sd Series
Type Values Removed Values Added
Metrics ssvc

{'options': {'Automatable': 'no', 'Exploitation': 'none', 'Technical Impact': 'partial'}, 'version': '2.0.3'}

Type Values Removed Values Added
Description A vulnerability exists in the command handling of the IEC 61850 communication stack included in the product revisions listed as affected in this CVE. An attacker with access to IEC 61850 networks could exploit the vulnera bility by using a specially crafted 61850 packet, forcing the communication interfaces of the PM 877, CI850 and CI868 modules into fault mode or causing unavailability of the S+ Operations 61850 connectivity, resulting in a denial-of-service situation.  The System 800xA IEC61850 Connect is not affected. Note: This vulnerability does not impact on the overall availability and functionality of the S+ Operations node, only the 61850 communication function.     This issue affects AC800M (System 800xA): from 6.0.0x through 6.0.0303.0, from 6.1.0x through 6.1.0031.0, from 6.1.1x through 6.1.1004.0, from 6.1.1x through 6.1.1202.0, from 6.2.0x through 6.2.0006.0; Symphony Plus SD Series: A_0, A_1, A_2.003, A_3.005, A_4.001, B_0.005; Symphony Plus MR (Melody Rack): from 3.10 through 3.52; S+ Operations: 2.1, 2.2, 2.3, 3.3.
Title Denial of Service Vulnerabilities in System 800xA, Symphony® Plus IEC 61850
Weaknesses CWE-1284
References
Metrics cvssV3_1

{'score': 6.5, 'vector': 'CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H'}

cvssV4_0

{'score': 7.1, 'vector': 'CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N'}

Weaknesses

Sources

Status
PUBLISHED
Assigner
ABB
Published
Updated
Apr 13, 2026, 6:03 PM
Reserved
Apr 17, 2025, 10:42 AM
Status
Deferred
Published
Apr 13, 2026, 6:16 PM
Modified
Oct 14, 2026, 5:10 PM