Metasys product command injection vulnerability could allow remote SQL execution
Default status is the baseline for the product, each version can override it (e.g. patched versions marked unaffected).
| Vendor | Product | Default status | Versions | ||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Johnson Controls | Metasys | unaffected |
|
No data.
No data.
| Vendor | Product | Versions |
|---|---|---|
| Johnsoncontrols | Metasys | — |
Vendor Solution
a. Follow the Johnson Controls hardening guide steps to ensure your Metasys installation is on a segmented network, not exposed to untrusted networks such as the internet b. Download and execute the Metasys patch for GIV-165989 from the License Portal https://software.jci.com/licenseportal/ . Login credentials are required c. Close incoming TCP port 1433 d. For more detailed mitigation instructions, please see Johnson Controls Product Security Advisory JCI-PSA-2026-02 at the following location: https://www.johnsoncontrols.com/cyber-solutions/security-advisories
No CVSS v3.1
No CVSS v3.0
No CVSS v2
This CVE is not in the KEV list.
Exploit prediction score: 1.5% (1.475% probability within 30 days)
| Type | Values Removed | Values Added |
|---|---|---|
| First Time appeared |
Johnsoncontrols
Johnsoncontrols metasys |
|
| Vendors & Products |
Johnsoncontrols
Johnsoncontrols metasys |
| Type | Values Removed | Values Added |
|---|---|---|
| Metrics |
ssvc
|
| Type | Values Removed | Values Added |
|---|---|---|
| Description | Johnson Controls Metasys component listed below have Improper Neutralization of Special Elements used in a Command (Command Injection) Vulnerability . Successful exploitation of this vulnerability could allow remote SQL execution This issue affects * Metasys: Application and Data Server (ADS) installed with SQL Express deployed as part of the Metasys 14.1 and prior installation, * Extended Application and Data Server (ADX) installed with SQL Express deployed as part of the Metasys 14.1 installation, * LCS8500 or NAE8500 installed with SQL Express deployed as part of the Metasys installation Releases 12.0 through 14.1, * System Configuration Tool (SCT) installed with SQL Express deployed as part of the SCT installation 17.1 and prior, * Controller Configuration Tool (CCT) installed with SQL Express deployed as part of the CCT installation 17.0 and prior. | |
| Title | Metasys product command injection vulnerability could allow remote SQL execution | |
| Weaknesses | CWE-77 | |
| References |
| |
| Metrics |
cvssV4_0
|