FactoryTalk View Machine Edition Vulnerable to Remote Code Execution
Default status is the baseline for the product, each version can override it (e.g. patched versions marked unaffected).
| Vendor | Product | Default status | Versions | ||||||
|---|---|---|---|---|---|---|---|---|---|
| Rockwell Automation | Fa | unaffected |
|
Configuration 1 [-]
| AND |
|
No data.
No data available yet.
Vendor Solution
* Install the security patches for the respective versions referencing BF29493 - Patch: FactoryTalk Linx CIP Vulnerability issue, FactoryTalk View ME 12.0, 13.0 https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1139946 .
| Source | ID | Title |
|---|---|---|
EUVD |
EUVD-2023-33597 | Rockwell Automation FactoryTalk View Machine Edition on the PanelView Plus, improperly verifies user’s input, which allows unauthenticated attacker to achieve remote code executed via crafted malicious packets. The device has the functionality, through a CIP class, to execute exported functions from libraries. There is a routine that restricts it to execute specific functions from two dynamic link library files. By using a CIP class, an attacker can upload a self-made library to the device which allows the attacker to bypass the security check and execute any code written in the function. |
No CVSS v4.0
No CVSS v3.0
No CVSS v2
This CVE is not in the KEV list.
Exploit prediction score: 17.3% (17.274% probability within 30 days)
| Type | Values Removed | Values Added |
|---|---|---|
| Metrics |
ssvc
|