Input Validation Vulnerability in Hitachi Energy’s MicroSCADA Pro/X SYS600 Products
Default status is the baseline for the product, each version can override it (e.g. patched versions marked unaffected).
| Vendor | Product | Default status | Versions | ||||||
|---|---|---|---|---|---|---|---|---|---|
| Hitachi Energy | MicroSCADA Pro SYS600 | unaffected |
|
||||||
| Hitachi Energy | MicroSCADA X SYS600 | unaffected |
|
Configuration 1 [-]
|
No data.
No data available yet.
Vendor Solution
For SYS600 9.x: update to at SYS600 version SYS600 9.4 FP2 Hotfix 5 when it is released or upgrade to at least SYS600 version 10.4.1. A requirement to install SYS600 9.4 FP2 Hotfix 5 is to have at least the SYS600 9.4 FP2 Hotfix 4 installed. CPE: cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.0:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.4:*:*:*:*:*:*:*
Vendor Workaround
Recommended security practices and firewall configurations can help protect a process control network from attacks that originate from outside the network. Such practices include that process control systems are physically protected from direct access by unauthorized personnel, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed, and others that have to be evaluated case by case. Process control systems should not be used for Internet surfing, instant messaging, or receiving e-mails. Portable computers and removable storage media should be carefully scanned for viruses before they are connected to a control system. Proper password policies and processes should be followed. We recommend following the cybersecurity deployment guideline as follows: 1MRK511518 MicroSCADA X Cyber Security Deployment Guideline.
| Source | ID | Title |
|---|---|---|
EUVD |
EUVD-2022-42766 | An input validation vulnerability exists in the Monitor Pro interface of MicroSCADA Pro and MicroSCADA X SYS600. An authenticated user can launch an administrator level remote code execution irrespective of the authenticated user's role. |
No CVSS v4.0
No CVSS v3.0
No CVSS v2
This CVE is not in the KEV list.
Exploit prediction score: < 1% (0.304% probability within 30 days)
Key SSVC decision points have not yet been added.
| Type | Values Removed | Values Added |
|---|---|---|
| Description | An input validation vulnerability exists in the Monitor Pro interface of MicroSCADA Pro and MicroSCADA X SYS600. An authenticated user can launch an administrator level remote code execution irrespective of the authenticated user's role. | An input validation vulnerability exists in the Monitor Pro interface of MicroSCADA Pro and MicroSCADA X SYS600. An authenticated user can launch an administrator level remote code execution irrespective of the authenticated user's role. |