Measuresoft ScadaPro Server Improper Access Control
Default status is the baseline for the product, each version can override it (e.g. patched versions marked unaffected).
| Vendor | Product | Default status | Versions | ||||||
|---|---|---|---|---|---|---|---|---|---|
| Measuresoft | ScadaPro Server | affected |
|
No data.
No data available yet.
Vendor Workaround
Measuresoft recommends the following steps to remove full access to the ORCHESTRATOR service: 1. Open a command-line window (CMD) with 'run as administrator' 2. Use the following command to make the permission change to the ORCHESTRATOR service: sc sdset ORCHESTRATOR D:(A;;CCLCSWRPWPDTLOCRRC;;;SY)(A;;CCDCLCSWRPWPDTLOCRSDRCWDWO;;;BA)(A;;CCLCSWLOCRRC;;;IU)(A;;CCLCSWLOCRRC;;;SU) 3. As a low-level user, attempt to shut down the ORCHESTRATOR service: sc stop ORCHESTRATOR. User will be denied. It will no longer be possible to edit the configuration of the service by a low-level user.
| Source | ID | Title |
|---|---|---|
EUVD |
EUVD-2022-42665 | The security descriptor of Measuresoft ScadaPro Server version 6.7 has inconsistent permissions, which could allow a local user with limited privileges to modify the service binary path and start malicious commands with SYSTEM privileges. |
No CVSS v4.0
No CVSS v3.0
No CVSS v2
This CVE is not in the KEV list.
Exploit prediction score: < 1% (0.261% probability within 30 days)
| Link | Providers |
|---|---|
| https://www.cisa.gov/uscert/ics/advisories/icsa-22-265-01 |
|
| Type | Values Removed | Values Added |
|---|---|---|
| Metrics |
ssvc
|