CVE-2022-28613

Specially Crafted Modbus TCP Packet Vulnerability in RTU500 series

Published May 2, 2022 CVSS 3.1 · 7.5 High EPSS < 1% KEV · Not listed
Description
A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is en-abled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the receiving RTU500 CMU to reboot. The vulnerability is caused by the validation error in the length information carried in MBAP header in the HCI Modbus TCP function.

Remediation

Vendor Solution

Remediation available, see the advisory for details.

Tracking

Sign in to view the affected projects.

Advisories

Source ID Title
EUVD EUVD EUVD-2022-33055 A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is en-abled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the receiving RTU500 CMU to reboot. The vulnerability is caused by the validation error in the length information carried in MBAP header in the HCI Modbus TCP function.
History
Type Values Removed Values Added
Metrics cvssV3_1

{'score': 10, 'vector': 'CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H'}

cvssV3_1

{'score': 7.5, 'vector': 'CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H'}

Type Values Removed Values Added
Description A vulnerability in the HCI Modbus TCP COMPONENT of Hitachi Energy RTU500 series CMU Firmware that is caused by the validation error in the length information carried in MBAP header allows an ATTACKER to reboot the device by sending a special crafted message. This issue affects: Hitachi Energy RTU500 series CMU Firmware 12.0.*; 12.2.*; 12.4.*; 12.6.*; 12.7.*; 13.2.*. A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is en-abled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the receiving RTU500 CMU to reboot. The vulnerability is caused by the validation error in the length information carried in MBAP header in the HCI Modbus TCP function.
References
Metrics cvssV3_1

{'score': 7.5, 'vector': 'CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H'}

cvssV3_1

{'score': 10, 'vector': 'CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H'}

Weaknesses

Sources

Status
PUBLISHED
Assigner
Hitachi Energy
Published
Updated
Sep 25, 2024, 7:58 AM
Reserved
Apr 4, 2022, 12:00 AM
Status
Modified
Published
May 2, 2022, 7:15 PM
Modified
Jun 17, 2026, 4:38 AM