Specially Crafted IEC 60870-5-104 Packet Vulnerability in RTU500 series
Default status is the baseline for the product, each version can override it (e.g. patched versions marked unaffected).
| Vendor | Product | Default status | Versions | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Hitachi Energy | RTU500 series | affected |
|
Configuration 1 [-]
| AND |
|
No data.
No data available yet.
Vendor Solution
- Disable BCI IEC 60870-5-104 function by configuration if it is not used. - Update to RTU500 series CMU Firmware version 12.6.5.0 or later (e.g., RTU500 CMU Firmware version 12.7.* or CMU Firmware version 13.2.* or later).
| Source | ID | Title |
|---|---|---|
EUVD |
EUVD-2021-22169 | Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function of Hitachi Energy RTU500 series allows an attacker to cause the receiving RTU500 CMU of which the BCI is enabled to reboot when receiving a specially crafted message. By default, BCI IEC 60870-5-104 function is disabled (not configured). This issue affects: Hitachi Energy RTU500 series CMU Firmware version 12.0.* (all versions); CMU Firmware version 12.2.* (all versions); CMU Firmware version 12.4.* (all versions). |
No CVSS v4.0
No CVSS v3.0
This CVE is not in the KEV list.
Exploit prediction score: < 1% (0.950% probability within 30 days)
Key SSVC decision points have not yet been added.
No history.