ENDRESS+HAUSER: Ecograph T utilizing Webserver firmware version 1.x has improper privilege management
Default status is the baseline for the product, each version can override it (e.g. patched versions marked unaffected).
| Vendor | Product | Default status | Versions | ||||||
|---|---|---|---|---|---|---|---|---|---|
| Endress+Hauser | RSG35 - Ecograph T | affected |
|
||||||
| Endress+Hauser | ORSG35 - Ecograph T Neutral/Private Label | affected |
|
Configuration 1 [-]
| AND |
|
Configuration 2 [-]
| AND |
|
Configuration 3 [-]
| AND |
|
Configuration 4 [-]
| AND |
|
No data.
No data available yet.
Vendor Solution
Endress+Hauser will not change this behavior. Customers are recommended to take the measures for Temporary Fix / Mitigation as described above.
Vendor Workaround
Customers should configure a perimeter firewall to block traffic from untrusted networks and users to the device. These recommendations will be incorporated into the device documentation (operating instructions). Change default password for operator, service and admin account.
| Source | ID | Title |
|---|---|---|
EUVD |
EUVD-2020-4797 | Endress+Hauser Ecograph T (Neutral/Private Label) (RSG35, ORSG35) with Firmware version prior to V2.0.0 is prone to improper privilege management. The affected device has a web-based user interface with a role-based access system. Users with different roles have different write and read privileges. The access system is based on dynamic "tokens". The vulnerability is that user sessions are not closed correctly and a user with fewer rights is assigned the higher rights when he logs on. |
No CVSS v4.0
No CVSS v3.0
This CVE is not in the KEV list.
Exploit prediction score: < 1% (0.920% probability within 30 days)
Key SSVC decision points have not yet been added.
| Link | Providers |
|---|---|
| https://cert.vde.com/en-us/advisories/vde-2020-021 |
|
No history.