Default status is the baseline for the product, each version can override it (e.g. patched versions marked unaffected).
| Vendor | Product | Default status | Versions | ||||||
|---|---|---|---|---|---|---|---|---|---|
| n/a | WAGO PFC200 Series | affected |
|
Configuration 1 [-]
| AND |
|
No data.
No data available yet.
| Source | ID | Title |
|---|---|---|
EUVD |
EUVD-2018-17229 | An Improper Authentication issue was discovered in WAGO PFC200 Series 3S CoDeSys Runtime versions 2.3.X and 2.4.X. An attacker can execute different unauthenticated remote operations because of the CoDeSys Runtime application, which is available via network by default on Port 2455. An attacker could execute some unauthenticated commands such as reading, writing, or deleting arbitrary files, or manipulate the PLC application during runtime by sending specially-crafted TCP packets to Port 2455. |
No CVSS v4.0
No CVSS v3.1
This CVE is not in the KEV list.
Exploit prediction score: 2.7% (2.676% probability within 30 days)
Key SSVC decision points have not yet been added.
| Link | Providers |
|---|---|
| https://ics-cert.us-cert.gov/advisories/ICSA-18-044-01 |
|
No history.