CVE-2012-4359

Published Aug 19, 2012 CVSS 2.0 · 9.3 Critical EPSS 2.5% KEV · Not listed
Description
Sielco Sistemi Winlog Pro SCADA before 2.07.18 and Winlog Lite SCADA before 2.07.18 do not validate the return value of the realloc function, which allows remote attackers to cause a denial of service (invalid 0x00 write operation and daemon crash) or possibly have unspecified other impact via a port-46824 TCP packet with a crafted negative integer after the opcode. NOTE: this vulnerability exists because of an incomplete fix for CVE-2012-4358.

Remediation

No solution or workaround provided in the CVE record

Tracking

Sign in to view the affected projects.

Advisories

Source ID Title
EUVD EUVD EUVD-2012-4302 Sielco Sistemi Winlog Pro SCADA before 2.07.18 and Winlog Lite SCADA before 2.07.18 do not validate the return value of the realloc function, which allows remote attackers to cause a denial of service (invalid 0x00 write operation and daemon crash) or possibly have unspecified other impact via a port-46824 TCP packet with a crafted negative integer after the opcode. NOTE: this vulnerability exists because of an incomplete fix for CVE-2012-4358.
History

No history.

Weaknesses

Sources

Status
PUBLISHED
Assigner
mitre
Published
Updated
Sep 16, 2024, 7:00 PM
Reserved
Aug 19, 2012, 12:00 AM
Status
Modified
Published
Aug 19, 2012, 8:55 PM
Modified
Jun 16, 2026, 11:44 PM