CVE-2014-0160

openssl: information disclosure in handling of TLS heartbeat extension packets

The (1) TLS and (2) DTLS implementations in OpenSSL 1.0.1 before 1.0.1g do not properly handle Heartbeat Extension packets, which allows remote attackers to obtain sensitive information from process memory via crafted packets that trigger a buffer over-read, as demonstrated by reading private keys, related to d1_both.c and t1_lib.c, aka the Heartbleed bug.

CVSS 3.1 · 7.5 High EPSS 100.0% KEV · Listed
Vendors
Broadcom Canonical Debian and 10 more
CVE-2017-12069

An XXE vulnerability has been identified in OPC Foundation UA .NET Sample Code before 2017-03-21 and Local Discovery Server (LDS) before 1.03.367. Among the affected products are Siemens SIMATIC PCS7 (All versions V8.1 and earlier), SIMATIC WinCC (All versions < V7.4 SP1), SIMATIC WinCC Runtime Professional (All versions < V14 SP1), SIMATIC NET PC Software, and SIMATIC IT Production Suite. By sending specially crafted packets to the OPC Discovery Server at port 4840/tcp, an attacker might cause the system to access various resources chosen by the attacker.

CVSS 3.0 · 8.2 High EPSS 2.9% KEV · Not listed
CVE-2014-4684

The database server in Siemens SIMATIC WinCC before 7.3, as used in PCS7 and other products, allows remote authenticated users to gain privileges via a request to TCP port 1433.

CVSS 2.0 · 6.0 Medium EPSS 1.3% KEV · Not listed
Vendors
Products
CVE-2015-2822

Siemens SIMATIC HMI Comfort Panels before WinCC (TIA Portal) 13 SP1 Upd2 and SIMATIC WinCC Runtime Advanced before WinCC (TIA Portal) 13 SP1 Upd2 allow man-in-the-middle attackers to cause a denial of service via crafted packets on TCP port 102.

CVSS 2.0 · 4.3 Medium EPSS 1.7% KEV · Not listed
Vendors
Products
CVE-2014-4683

The WebNavigator server in Siemens SIMATIC WinCC before 7.3, as used in PCS7 and other products, allows remote authenticated users to gain privileges via a (1) HTTP or (2) HTTPS request.

CVSS 2.0 · 4.9 Medium EPSS 1.2% KEV · Not listed
Vendors
Products
CVE-2014-4682

The WebNavigator server in Siemens SIMATIC WinCC before 7.3, as used in PCS7 and other products, allows remote attackers to obtain sensitive information via an HTTP request.

CVSS 2.0 · 5.0 Medium EPSS 1.7% KEV · Not listed
Vendors
Products
CVE-2015-1358

The remote-management module in the (1) Multi Panels, (2) Comfort Panels, and (3) RT Advanced functionality in Siemens SIMATIC WinCC (TIA Portal) before 13 SP1 and in the (4) panels and (5) runtime functionality in SIMATIC WinCC flexible before 2008 SP3 Up7 does not properly encrypt credentials in transit, which makes it easier for remote attackers to determine cleartext credentials by sniffing the network and conducting a decryption attack.

CVSS 2.0 · 5.0 Medium EPSS 2.7% KEV · Not listed
Vendors
Products
CVE-2014-4686

The Project administration application in Siemens SIMATIC WinCC before 7.3, as used in PCS7 and other products, has a hardcoded encryption key, which allows remote attackers to obtain sensitive information by extracting this key from another product installation and then employing this key during the sniffing of network traffic on TCP port 1030.

CVSS 2.0 · 6.8 Medium EPSS 1.1% KEV · Not listed
Vendors
Products
CVE-2015-2823

Siemens SIMATIC HMI Basic Panels 2nd Generation before WinCC (TIA Portal) 13 SP1 Upd2, SIMATIC HMI Comfort Panels before WinCC (TIA Portal) 13 SP1 Upd2, SIMATIC WinCC Runtime Advanced before WinCC (TIA Portal) 13 SP1 Upd2, SIMATIC WinCC Runtime Professional before WinCC (TIA Portal) 13 SP1 Upd2, SIMATIC HMI Basic Panels 1st Generation (WinCC TIA Portal), SIMATIC HMI Mobile Panel 277 (WinCC TIA Portal), SIMATIC HMI Multi Panels (WinCC TIA Portal), and SIMATIC WinCC 7.x before 7.3 Upd4 allow remote attackers to complete authentication by leveraging knowledge of a password hash without knowledge of the associated password.

CVSS 2.0 · 6.8 Medium EPSS 2.1% KEV · Not listed
Vendors
CVE-2014-4685

Siemens SIMATIC WinCC before 7.3, as used in PCS7 and other products, allows local users to gain privileges by leveraging weak system-object access control.

CVSS 2.0 · 4.6 Medium EPSS < 1% KEV · Not listed
Vendors
Products
CVE-2011-4514

The TELNET daemon in Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 (aka TIA portal); the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime does not perform authentication, which makes it easier for remote attackers to obtain access via a TCP session.

CVSS 2.0 · 10.0 Critical EPSS 3.4% KEV · Not listed
Vendors
CVE-2011-4879

miniweb.exe in the HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 (aka TIA portal) before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime does not properly handle URIs beginning with a 0xfa character, which allows remote attackers to read data from arbitrary memory locations or cause a denial of service (application crash) via a crafted POST request.

CVSS 2.0 · 8.5 High EPSS 12.1% KEV · Not listed
Vendors
CVE-2012-2595

Multiple cross-site scripting (XSS) vulnerabilities in unspecified web applications in Siemens WinCC 7.0 SP3 before Update 2 allow remote attackers to inject arbitrary web script or HTML via vectors involving special characters in parameters.

CVSS 2.0 · 4.3 Medium EPSS 1.5% KEV · Not listed
Vendors
Products
CVE-2012-2596

The XPath functionality in unspecified web applications in Siemens WinCC 7.0 SP3 before Update 2 does not properly handle special characters in parameters, which allows remote authenticated users to read or modify settings via a crafted URL, related to an "XML injection" attack.

CVSS 2.0 · 5.5 Medium EPSS 1.5% KEV · Not listed
Vendors
Products
CVE-2011-4878

Directory traversal vulnerability in miniweb.exe in the HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 (aka TIA portal) before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime allows remote attackers to read arbitrary files via a ..%5c (dot dot backslash) in a URI.

CVSS 2.0 · 7.8 High EPSS 11.1% KEV · Not listed
Vendors
CVE-2011-4513

Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 (aka TIA portal); the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime allow user-assisted remote attackers to execute arbitrary code via a crafted project file, related to the HMI web server and runtime loader.

CVSS 2.0 · 10.0 Critical EPSS 4.8% KEV · Not listed
Vendors
CVE-2011-4510

Cross-site scripting (XSS) vulnerability in the HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 (aka TIA portal) before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime allows remote attackers to inject arbitrary web script or HTML via unspecified vectors, a different vulnerability than CVE-2011-4511.

CVSS 2.0 · 4.3 Medium EPSS 1.4% KEV · Not listed
Vendors
CVE-2011-4877

HmiLoad in the runtime loader in Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 (aka TIA portal); the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime, when Transfer Mode is enabled, allows remote attackers to cause a denial of service (application crash) by sending crafted data over TCP.

CVSS 2.0 · 7.1 High EPSS 7.3% KEV · Not listed
Vendors
CVE-2012-3030

WebNavigator in Siemens WinCC 7.0 SP3 and earlier, as used in SIMATIC PCS7 and other products, stores sensitive information under the web root with insufficient access control, which allows remote attackers to read a (1) log file or (2) configuration file via a direct request.

CVSS 2.0 · 5.0 Medium EPSS 2.6% KEV · Not listed
Vendors
Products
CVE-2011-4876

Directory traversal vulnerability in HmiLoad in the runtime loader in Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 (aka TIA portal); the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime, when Transfer Mode is enabled, allows remote attackers to execute, read, create, modify, or delete arbitrary files via a .. (dot dot) in a string.

CVSS 2.0 · 9.3 Critical EPSS 9.0% KEV · Not listed