CVE-2025-40943

Affected devices do not properly sanitize contents of trace files. This could allow an attacker to inject code through social engineering an authorized user, who has the function right "Read diagnostics", to import a specially crafted trace file. The malicious trace file is insufficiently sanitized and malicious code could be executed in the clients browser session and trigger PLC operations via the webserver that the legitimate user is authorized to perform.

CVE-2023-28831

The OPC UA implementations (ANSI C and C++) in affected products contain an integer overflow vulnerability that could cause the application to run into an infinite loop during certificate validation. This could allow an unauthenticated remote attacker to create a denial of service condition by sending a specially crafted certificate.

CVSS 4.0 · 8.7 High EPSS 1.1% KEV · Not listed
Vendors
CVE-2022-38465

A vulnerability has been identified in SIMATIC Drive Controller family (All versions < V2.9.2), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V21.9), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.5.0), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.9.2), SIMATIC S7-1500 Software Controller (All versions < V21.9), SIMATIC S7-PLCSIM Advanced (All versions < V4.0), SINUMERIK MC (All versions < V6.21), SINUMERIK ONE (All versions < V6.21). Affected products protect the built-in global private key in a way that cannot be considered sufficient any longer. The key is used for the legacy protection of confidential configuration data and the legacy PG/PC and HMI communication. This could allow attackers to discover the private key of a CPU product family by an offline attack against a single CPU of the family. Attackers could then use this knowledge to extract confidential configuration data from projects that are protected by that key or to perform attacks against legacy PG/PC and HMI communication.

CVSS 3.1 · 9.3 Critical EPSS < 1% KEV · Not listed
Vendors
CVE-2021-37185

A vulnerability has been identified in SIMATIC Drive Controller family (All versions >= V2.9.2 < V2.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V21.9 < V21.9.4), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions >= V4.5.0 < V4.5.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.9.2 < V2.9.4), SIMATIC S7-1500 Software Controller (All versions >= V21.9 < V21.9.4), SIMATIC S7-PLCSIM Advanced (All versions >= V4.0 < V4.0 SP1), SIPLUS TIM 1531 IRC (All versions < V2.3.6), TIM 1531 IRC (All versions < V2.3.6). An unauthenticated attacker could cause a denial-of-service condition in a PLC when sending specially prepared packets over port 102/tcp. A restart of the affected device is needed to restore normal operations.

CVE-2021-37204

A vulnerability has been identified in SIMATIC Drive Controller family (All versions < V2.9.2), SIMATIC Drive Controller family (All versions >= V2.9.2 < V2.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V21.9), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V21.9 < V21.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 Ready4Linux (All versions), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.5.0), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions >= V4.5.0 < V4.5.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.9.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.9.2 < V2.9.4), SIMATIC S7-1500 Software Controller (All versions < V21.9), SIMATIC S7-1500 Software Controller (All versions >= V21.9 < V21.9.4), SIMATIC S7-PLCSIM Advanced (All versions < V4.0), SIMATIC S7-PLCSIM Advanced (All versions >= V4.0 < V4.0 SP1), SIPLUS TIM 1531 IRC (All versions < V2.3.6), TIM 1531 IRC (All versions < V2.3.6). An unauthenticated attacker could cause a denial-of-service condition in a PLC when sending specially prepared packet over port 102/tcp. A restart of the affected device is needed to restore normal operations.

CVE-2021-37205

A vulnerability has been identified in SIMATIC Drive Controller family (All versions >= V2.9.2 < V2.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V21.9 < V21.9.4), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions >= V4.5.0 < V4.5.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.9.2 < V2.9.4), SIMATIC S7-1500 Software Controller (All versions >= V21.9 < V21.9.4), SIMATIC S7-PLCSIM Advanced (All versions >= V4.0 < V4.0 SP1), SIPLUS TIM 1531 IRC (All versions < V2.3.6), TIM 1531 IRC (All versions < V2.3.6). An unauthenticated attacker could cause a denial-of-service condition in a PLC when sending specially prepared packets over port 102/tcp. A restart of the affected device is needed to restore normal operations.

CVE-2022-38773

Affected devices do not contain an Immutable Root of Trust in Hardware. With this the integrity of the code executed on the device can not be validated during load-time. An attacker with physical access to the device could use this to replace the boot image of the device and execute arbitrary code.

CVSS 3.1 · 4.6 Medium EPSS < 1% KEV · Not listed
Vendors
CVE-2021-42029

A vulnerability has been identified in SIMATIC STEP 7 (TIA Portal) V15 (All versions), SIMATIC STEP 7 (TIA Portal) V16 (All versions < V16 Update 5), SIMATIC STEP 7 (TIA Portal) V17 (All versions < V17 Update 2). An attacker could achieve privilege escalation on the web server of certain devices due to improper access control vulnerability in the engineering system software. The attacker needs to have direct access to the impacted web server.

CVSS 3.1 · 7.8 High EPSS < 1% KEV · Not listed
Vendors
CVE-2019-10943

A vulnerability has been identified in SIMATIC Drive Controller family (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V20.8), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V20.8), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.4.0), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions >= V4.4.0), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.8.1), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.8.1), SIMATIC S7-1500 Software Controller (All versions < V20.8), SIMATIC S7-1500 Software Controller (All versions >= V20.8), SIMATIC S7-PLCSIM Advanced (All versions < V3.0), SIMATIC S7-PLCSIM Advanced (All versions >= V3.0). An attacker with network access to port 102/tcp could potentially modify the user program on the PLC in a way that the running code is different from the source code which is stored on the device. An attacker must have network access to affected devices and must be able to perform changes to the user program. The vulnerability could impact the perceived integrity of the user program stored on the CPU. An engineer that tries to obtain the code of the user program running on the device, can receive different source code that is not actually running on the device.

CVE-2019-10929

A vulnerability has been identified in SIMATIC CP 1626 (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V20.8), SIMATIC HMI Panel (incl. SIPLUS variants) (All versions), SIMATIC NET PC Software V14 (All versions < V14 SP1 Update 14), SIMATIC NET PC Software V15 (All versions), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.4.0), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.8.1), SIMATIC S7-1500 Software Controller (All versions < V20.8), SIMATIC S7-PLCSIM Advanced (All versions < V3.0), SIMATIC STEP 7 (TIA Portal) (All versions < V16), SIMATIC WinCC (TIA Portal) (All versions < V16), SIMATIC WinCC OA (All versions < V3.16 P013), SIMATIC WinCC Runtime Advanced (All versions < V16), SIMATIC WinCC Runtime Professional (All versions < V16), TIM 1531 IRC (incl. SIPLUS NET variants) (All versions < V2.1). Affected devices contain a message protection bypass vulnerability due to certain properties in the calculation used for integrity protection. This could allow an attacker in a Man-in-the-Middle position to modify network traffic sent on port 102/tcp to the affected devices.

CVSS 3.1 · 5.9 Medium EPSS < 1% KEV · Not listed