LOYTEC LINX-151, LINX-212, LVIS-3ME12-A1, LIOB-586, LIOB-580 V2, LIOB-588, L-INX Configurator devices (all versions) use cleartext HTTP for login.
Search vulnerabilities
LOYTEC LINX-151, LINX-212, LVIS-3ME12-A1, LIOB-586, LIOB-580 V2, LIOB-588, L-INX Configurator devices (all versions) lack authentication for the preinstalled version of LWEB-802 via an lweb802_pre/ URI. An unauthenticated attacker can edit any project (or create a new project) and control its GUI.
LOYTEC LINX-151, LINX-212, LVIS-3ME12-A1, LIOB-586, LIOB-580 V2, LIOB-588, L-INX Configurator devices (all versions) send password-change requests via cleartext HTTP.
An Insufficient Entropy issue was discovered in LOYTEC LVIS-3ME versions prior to 6.2.0. The application does not utilize sufficiently random number generation for the web interface authentication mechanism, which could allow remote code execution.
An Insufficiently Protected Credentials issue was discovered in LOYTEC LVIS-3ME versions prior to 6.2.0. The application does not sufficiently protect sensitive information from unauthorized access.
A Cross-site Scripting issue was discovered in LOYTEC LVIS-3ME versions prior to 6.2.0. The web interface lacks proper web request validation, which could allow XSS attacks to occur if an authenticated user of the web interface is tricked into clicking a malicious link.
A Relative Path Traversal issue was discovered in LOYTEC LVIS-3ME versions prior to 6.2.0. The web user interface fails to prevent access to critical files that non administrative users should not have access to, which could allow an attacker to create or modify files or execute arbitrary code.