CVE-2026-3611

Honeywell IQ4x BMS Controller Missing authentication for critical function

The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.

CVSS 4.0 · 10 Critical EPSS 6.3% KEV · Not listed
Vendors
Products
Iq3 Iq412 Iq412 Firmware and 9 more
CVE-2024-46453

A cross-site scripting (XSS) vulnerability in the component /test/ of iq3xcite v2.31 to v3.05 allows attackers to execute arbitrary web scripts or HTML via a crafted payload.

CVSS 3.1 · 6.1 Medium EPSS < 1% KEV · Not listed