Search vulnerabilities

Results 417

Export CSV
CVE-2017-6015

Without quotation marks, any whitespace in the file path for Rockwell Automation FactoryTalk Activation version 4.00.02 remains ambiguous, which may allow an attacker to link to or run a malicious executable. This may allow an authorized, but not privileged local user to execute arbitrary code with elevated privileges on the system. CVSS v3 base score: 8.8, CVSS vector string: (AV:L/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H). Rockwell Automation has released a new version of FactoryTalk Activation, Version 4.01, which addresses the identified vulnerability. Rockwell Automation recommends upgrading to the latest version of FactoryTalk Activation, Version 4.01 or later.

CVSS 3.0 · 7.8 High EPSS < 1% KEV · Not listed
CVE-2017-16740

A Buffer Overflow issue was discovered in Rockwell Automation Allen-Bradley MicroLogix 1400 Controllers, Series B and C Versions 21.002 and earlier. The stack-based buffer overflow vulnerability has been identified, which may allow remote code execution.

CVSS 3.0 · 10.0 Critical EPSS 7.2% KEV · Not listed
CVE-2017-14473

An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: Any Description: Reads the encoded ladder logic from its data file and print it out in HEX.

CVSS 3.0 · 10 Critical EPSS 38.0% KEV · Not listed
CVE-2017-14472

An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: Any Description: Requests a specific set of bytes from an undocumented data file and returns the ASCII version of the master password.

CVSS 3.0 · 10 Critical EPSS 38.0% KEV · Not listed
CVE-2017-14471

An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG Associated Fault Codes: 0023, 002e, and 0037 Fault Type: Recoverable Description: The STI, EII, and HSC function files contain bits signifying whether or not a fault has occurred. Additionally there is a bit signaling the module to auto start. When these bits are set for any of the three modules and the device is moved into a run state, a fault is triggered.

CVSS 3.0 · 10 Critical EPSS 38.0% KEV · Not listed
CVE-2017-14470

An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG or RUN Description: The value 0xffffffff is considered NaN for the Float data type. When a float is set to this value and used in the PLC, a fault is triggered. NOTE: This is not possible through RSLogix.

CVSS 3.0 · 10 Critical EPSS 38.0% KEV · Not listed
CVE-2017-14469

An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG Associated Fault Code: 0028 Fault Type: Non-User Description: Values 0x01 and 0x02 are invalid values for the user fault routine. By writing directly to the file it is possible to set these values. When this is done and the device is moved into a run state, a fault is triggered. NOTE: This is not possible through RSLogix.

CVSS 3.0 · 10 Critical EPSS 38.0% KEV · Not listed
CVE-2017-14468

An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG Description: This ability is leveraged in a larger exploit to flash custom firmware.

CVSS 3.1 · 9.8 Critical EPSS 38.0% KEV · Not listed
CVE-2017-14467

An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE Description: Live rung edits are able to be made by an unauthenticated user allowing for addition, deletion, or modification of existing ladder logic. Additionally, faults and cpu state modification can be triggered if specific ladder logic is used.

CVSS 3.1 · 9.8 Critical EPSS 37.3% KEV · Not listed
CVE-2017-14466

An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG Description: The filetype 0x03 allows users write access, allowing the ability to overwrite the Master Password value stored in the file.

CVSS 3.1 · 9.8 Critical EPSS 38.0% KEV · Not listed
CVE-2017-14465

An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE Description: Any input or output can be forced, causing unpredictable activity from the PLC.

CVSS 3.1 · 9.8 Critical EPSS 35.2% KEV · Not listed
CVE-2017-14464

An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability.Required Keyswitch State: REMOTE or PROG Associated Fault Code: 0001 Fault Type: Non-User Description: A fault state can be triggered by setting the NVRAM/memory module user program mismatch bit (S2:9) when a memory module is NOT installed.

CVSS 3.1 · 9.8 Critical EPSS 38.0% KEV · Not listed
CVE-2017-14463

An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG Associated Fault Code: 0012 Fault Type: Non-User Description: A fault state can be triggered by overwriting the ladder logic data file (type 0x22 number 0x02) with null values.

CVSS 3.1 · 9.8 Critical EPSS 38.9% KEV · Not listed
CVE-2017-14462

An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG (also RUN for some) Description: Allows an attacker to enable SNMP, Modbus, DNP, and any other features in the channel configuration. Also allows attackers to change network parameters, such as IP address, name server, and domain name.

CVSS 3.1 · 9.8 Critical EPSS 35.2% KEV · Not listed
CVE-2017-12093

An exploitable insufficient resource pool vulnerability exists in the session communication functionality of Allen Bradley Micrologix 1400 Series B Firmware 21.2 and before. A specially crafted stream of packets can cause a flood of the session resource pool resulting in legitimate connections to the PLC being disconnected. An attacker can send unauthenticated packets to trigger this vulnerability.

CVSS 3.1 · 5.3 Medium EPSS 6.0% KEV · Not listed
CVE-2017-12092

An exploitable file write vulnerability exists in the memory module functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a file write resulting in a new program being written to the memory module. An attacker can send an unauthenticated packet to trigger this vulnerability.

CVSS 3.0 · 3.7 Low EPSS 2.7% KEV · Not listed
CVE-2017-12090

An exploitable denial of service vulnerability exists in the processing of snmp-set commands of the Allen Bradley Micrologix 1400 Series B FRN 21.2 and below. A specially crafted snmp-set request, when sent without associated firmware flashing snmp-set commands, can cause a device power cycle resulting in downtime for the device. An attacker can send one packet to trigger this vulnerability.

CVSS 3.0 · 7.7 High EPSS 4.7% KEV · Not listed
CVE-2017-12089

An exploitable denial of service vulnerability exists in the program download functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a device fault resulting in halted operations. An attacker can send an unauthenticated packet to trigger this vulnerability.

CVSS 3.0 · 8.6 High EPSS 4.8% KEV · Not listed
CVE-2017-12088

An exploitable denial of service vulnerability exists in the Ethernet functionality of the Allen Bradley Micrologix 1400 Series B FRN 21.2 and below. A specially crafted packet can cause a device power cycle resulting in a fault state and deletion of ladder logic. An attacker can send one unauthenticated packet to trigger this vulnerability

CVSS 3.0 · 8.6 High EPSS 4.6% KEV · Not listed
CVE-2013-2807

Rockwell Automation RSLinx Enterprise Software (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 does not handle input correctly and results in a logic error if it calculates an incorrect value for the “Total Record Size” field. By sending a datagram to the service over Port 4444/UDP with the “Record Data Size” field modified to a specifically oversized value, the service will calculate an undersized value for the “Total Record Size” that will cause an out-of-bounds read access violation that leads to a service crash. The service can be recovered with a manual reboot. The patches and details pertaining to these vulnerabilities can be found at the following Rockwell Automation Security Advisory link (login is required): https://rockwellautomation.custhelp.com/app/answers/detail/a_id/537599

CVSS 3.0 · 7.5 High EPSS 3.9% KEV · Not listed