CVE-2020-6084

An exploitable denial of service vulnerability exists in the ENIP Request Path Logical Segment functionality of Allen-Bradley Flex IO 1794-AENT/B 4.003. A specially crafted network request can cause a loss of communications with the device resulting in denial-of-service. An attacker can send a malicious packet to trigger this vulnerability by sending an Electronic Key Segment with less bytes than required by the Key Format Table.

CVSS 3.1 · 7.5 High EPSS 4.3% KEV · Not listed
CVE-2020-6083

An exploitable denial of service vulnerability exists in the ENIP Request Path Port Segment functionality of Allen-Bradley Flex IO 1794-AENT/B. A specially crafted network request can cause a loss of communications with the device resulting in denial-of-service. An attacker can send a malicious packet to trigger this vulnerability.

CVSS 3.1 · 7.5 High EPSS 4.2% KEV · Not listed
CVE-2020-5807

An unauthenticated remote attacker can send data to RsvcHost.exe listening on TCP port 5241 to add entries in the FactoryTalk Diagnostics event log. The attacker can specify long fields in the log entry, which can cause an unhandled exception in wcscpy_s() if a local user opens FactoryTalk Diagnostics Viewer (FTDiagViewer.exe) to view the log entry. Observed in FactoryTalk Diagnostics 6.11. All versions of FactoryTalk Diagnostics are affected.

CVSS 3.1 · 7.5 High EPSS 39.3% KEV · Not listed
CVE-2020-5806

An attacker-controlled memory allocation size can be passed to the C++ new operator in the CServerManager::HandleBrowseLoadIconStreamRequest in messaging.dll. This can be done by sending a specially crafted message to 127.0.0.1:7153. Observed in FactoryTalk Linx 6.11. All versions of FactoryTalk Linx are affected.

CVSS 3.1 · 5.5 Medium EPSS 4.8% KEV · Not listed
Products
CVE-2020-5802

An attacker-controlled memory allocation size can be passed to the C++ new operator in RnaDaSvr.dll by sending a specially crafted ConfigureItems message to TCP port 4241. This will cause an unhandled exception, resulting in termination of RSLinxNG.exe. Observed in FactoryTalk 6.11. All versions of FactoryTalk Linx are affected.

CVSS 3.1 · 7.5 High EPSS 44.7% KEV · Not listed
Products
CVE-2020-5801

An attacker can craft and send an OpenNamespace message to port 4241 with valid session-id that triggers an unhandled exception in CFTLDManager::HandleRequest function in RnaDaSvr.dll, resulting in process termination. Observed in FactoryTalk Linx 6.11. All versions of FactoryTalk Linx are affected.

CVSS 3.1 · 7.5 High EPSS 29.7% KEV · Not listed
Products
CVE-2020-27267

KEPServerEX v6.0 to v6.9, ThingWorx Kepware Server v6.8 and v6.9, ThingWorx Industrial Connectivity (all versions), OPC-Aggregator (all versions), Rockwell Automation KEPServer Enterprise, GE Digital Industrial Gateway Server v7.68.804 and v7.66, and Software Toolbox TOP Server all 6.x versions, are vulnerable to a heap-based buffer overflow. Opening a specifically crafted OPC UA message could allow an attacker to crash the server and potentially leak data.

CVSS 3.1 · 9.1 Critical EPSS 6.0% KEV · Not listed
Vendors
CVE-2020-27265

KEPServerEX: v6.0 to v6.9, ThingWorx Kepware Server: v6.8 and v6.9, ThingWorx Industrial Connectivity: All versions, OPC-Aggregator: All versions, Rockwell Automation KEPServer Enterprise, GE Digital Industrial Gateway Server: v7.68.804 and v7.66, Software Toolbox TOP Server: All 6.x versions are vulnerable to a stack-based buffer overflow. Opening a specifically crafted OPC UA message could allow an attacker to crash the server and remotely execute code.

CVSS 3.1 · 9.8 Critical EPSS 12.5% KEV · Not listed
Vendors
CVE-2020-27263

KEPServerEX: v6.0 to v6.9, ThingWorx Kepware Server: v6.8 and v6.9, ThingWorx Industrial Connectivity: All versions, OPC-Aggregator: All versions, Rockwell Automation KEPServer Enterprise, GE Digital Industrial Gateway Server: v7.68.804 and v7.66, Software Toolbox TOP Server: All 6.x versions, are vulnerable to a heap-based buffer overflow. Opening a specifically crafted OPC UA message could allow an attacker to crash the server and potentially leak data.

CVSS 3.1 · 9.1 Critical EPSS 6.0% KEV · Not listed
Vendors
CVE-2020-27255

A heap overflow vulnerability exists within FactoryTalk Linx Version 6.11 and prior. This vulnerability could allow a remote, unauthenticated attacker to send malicious set attribute requests, which could result in the leaking of sensitive information. This information disclosure could lead to the bypass of address space layout randomization (ASLR).

CVSS 3.1 · 7.5 High EPSS 3.9% KEV · Not listed
Products
CVE-2020-27253

A flaw exists in the Ingress/Egress checks routine of FactoryTalk Linx Version 6.11 and prior. This vulnerability could allow a remote, unauthenticated attacker to specifically craft a malicious packet resulting in a denial-of-service condition on the device.

CVSS 3.1 · 7.5 High EPSS 1.9% KEV · Not listed
Products
CVE-2020-27251

A heap overflow vulnerability exists within FactoryTalk Linx Version 6.11 and prior. This vulnerability could allow a remote, unauthenticated attacker to send malicious port ranges, which could result in remote code execution.

CVSS 3.1 · 9.8 Critical EPSS 6.8% KEV · Not listed
Products
CVE-2020-14516

In Rockwell Automation FactoryTalk Services Platform Versions 6.10.00 and 6.11.00, there is an issue with the implementation of the SHA-256 hashing algorithm with FactoryTalk Services Platform that prevents the user password from being hashed properly.

CVSS 3.1 · 10.0 Critical EPSS 4.2% KEV · Not listed
CVE-2020-13573

A denial-of-service vulnerability exists in the Ethernet/IP server functionality of Rockwell Automation RSLinx Classic 2.57.00.14 CPR 9 SR 3. A specially crafted network request can lead to a denial of service. An attacker can send a sequence of malicious packets to trigger this vulnerability.

CVSS 3.1 · 7.5 High EPSS 5.6% KEV · Not listed
Products
CVE-2020-12038

Products that use EDS Subsystem: Version 28.0.1 and prior (FactoryTalk Linx software (Previously called RSLinx Enterprise): Versions 6.00, 6.10, and 6.11, RSLinx Classic: Version 4.11.00 and prior, RSNetWorx software: Version 28.00.00 and prior, Studio 5000 Logix Designer software: Version 32 and prior) is vulnerable. A memory corruption vulnerability exists in the algorithm that matches square brackets in the EDS subsystem. This may allow an attacker to craft specialized EDS files to crash the EDSParser COM object, leading to denial-of-service conditions.

CVSS 3.1 · 5.5 Medium EPSS 2.6% KEV · Not listed
Products
CVE-2020-12034

Products that use EDS Subsystem: Version 28.0.1 and prior (FactoryTalk Linx software (Previously called RSLinx Enterprise): Versions 6.00, 6.10, and 6.11, RSLinx Classic: Version 4.11.00 and prior, RSNetWorx software: Version 28.00.00 and prior, Studio 5000 Logix Designer software: Version 32 and prior) is vulnerable.The EDS subsystem does not provide adequate input sanitation, which may allow an attacker to craft specialized EDS files to inject SQL queries and manipulate the database storing the EDS files. This can lead to denial-of-service conditions.

CVSS 3.1 · 8.2 High EPSS 1.3% KEV · Not listed
Products
CVE-2020-12033

In Rockwell Automation FactoryTalk Services Platform, all versions, the redundancy host service (RdcyHost.exe) does not validate supplied identifiers, which could allow an unauthenticated, adjacent attacker to execute remote COM objects with elevated privileges.

CVSS 3.1 · 8.8 High EPSS 1.1% KEV · Not listed
CVE-2020-12031

Rockwell Automation FactoryTalk View SE

In all versions of FactoryTalk View SE, after bypassing memory corruption mechanisms found in the operating system, a local, authenticated attacker may corrupt the associated memory space allowing for arbitrary code execution. Rockwell Automation recommends applying patch 1126290. Before installing this patch, the patch rollup dated 06 Apr 2020 or later MUST be applied. 1066644 – Patch Roll-up for CPR9 SRx.

CVSS 3.1 · 7.5 High EPSS < 1% KEV · Not listed
Products
CVE-2020-12029

Rockwell Automation FactoryTalk View SE

All versions of FactoryTalk View SE do not properly validate input of filenames within a project directory. A remote, unauthenticated attacker may be able to execute a crafted file on a remote endpoint that may result in remote code execution (RCE). Rockwell Automation recommends applying patch 1126289. Before installing this patch, the patch rollup dated 06 Apr 2020 or later MUST be applied. 1066644 – Patch Roll-up for CPR9 SRx.

CVSS 3.1 · 9 Critical EPSS 47.0% KEV · Not listed
Products
CVE-2020-12028

Rockwell Automation FactoryTalk View SE

In all versions of FactoryTalk View SEA remote, an authenticated attacker may be able to utilize certain handlers to interact with the data on the remote endpoint since those handlers do not enforce appropriate permissions. Rockwell Automation recommends enabling built in security features found within FactoryTalk View SE. Users should follow guidance found in knowledge base articles 109056 and 1126943 to set up IPSec and/or HTTPs.

CVSS 3.1 · 7.3 High EPSS 53.0% KEV · Not listed